United States-MEPS-Electric chillers - 2003

Source: International Energy Agency
Last updated: 05 November 2017

The Federal Energy Management Program (FEMP) set efficiency requirements for air-cooled and water-cooled electric chillers. Product performance must be measured in accordance with AHRI 550/590 test procedures. Free-cooling and combination chiller-heat pump units are excluded.



 



Air-Cooled, All Compressors




  • Capacity: < 150 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 10.500

      • Integrated Part-Load Value (IPLV): 13.700


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 9.700

      • Integrated Part-Load Value (IPLV): 15.800



  • Capacity: = 150 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 10.700

      • Integrated Part-Load Value (IPLV): 14.000


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 9.700

      • Integrated Part-Load Value (IPLV): 16.100





 



Water-cooled, Positive Displacement




  • Capacity: < 75 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.736

      • Integrated Part-Load Value (IPLV): 0.600


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.780

      • Integrated Part-Load Value (IPLV): 0.500



  • Capacity: 75 to 149 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.715

      • Integrated Part-Load Value (IPLV): 0.560


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.750

      • Integrated Part-Load Value (IPLV): 0.490



  • Capacity: 150 to 299 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.651

      • Integrated Part-Load Value (IPLV): 0.540


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.680

      • Integrated Part-Load Value (IPLV): 0.440



  • Capacity: 300 to 599 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.610

      • Integrated Part-Load Value (IPLV): 0.520


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.625

      • Integrated Part-Load Value (IPLV): 0.410



  • Capacity: = 600 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.560

      • Integrated Part-Load Value (IPLV): 0.500


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.585

      • Integrated Part-Load Value (IPLV): 0.380





 



Water-cooled, Centrifugal




  • Capacity: < 150 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.610

      • Integrated Part-Load Value (IPLV): 0.550


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.695

      • Integrated Part-Load Value (IPLV): 0.440



  • Capacity: 150 to 299 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.610

      • Integrated Part-Load Value (IPLV): 0.550


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.635

      • Integrated Part-Load Value (IPLV): 0.400



  • Capacity: 300 to 399 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.560

      • Integrated Part-Load Value (IPLV): 0.520


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.595

      • Integrated Part-Load Value (IPLV): 0.390



  • Capacity: 400 to 599 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.560

      • Integrated Part-Load Value (IPLV): 0.500


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.585

      • Integrated Part-Load Value (IPLV): 0.380



  • Capacity: = 600 tons


    • Full-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.560

      • Integrated Part-Load Value (IPLV): 0.500


    • Part-Load Optimized Applications (products must meet both levels)


      • Full Load Efficiency: 0.585

      • Integrated Part-Load Value (IPLV): 0.380