Electric Chillers with over 350kW of capacity

Source: International Energy Agency
Last updated: 03 June 2020

As of December 2012 Chillers with capacities greater than 350kW sold in Australia must comply with the minimum energy



performance standards (MEPS) regulations.



 



Capacity: 350-499




  • Minimum COP


    • Air cooled 2.70

    • Water cooled 5.00


  • Minimum IPLV


    • Air cooled 3.70

    • Water cooled 5.50




Capacity: 500-699




  • Minimum COP


    • Air cooled 2.70

    • Water cooled 5.10


  • Minimum IPLV


    • Air cooled 3.70

    • Water cooled 6.00




Capacity: 700-999




  • Minimum COP


    • Air cooled 2.70

    • Water cooled 5.50


  • Minimum IPLV


    • Air cooled 4.10

    • Water cooled 6.20




Capacity: 1,000-1,499




  • Minimum COP


    • Air cooled 2.70

    • Water cooled 5.80


  • Minimum IPLV


    • Air cooled 4.10

    • Water cooled 6.50




Capacity: >1,500




  • Minimum COP


    • Air cooled 2.70

    • Water cooled 6.00


  • Minimum IPLV


    • Air cooled 4.10

    • Water cooled 6.50