SNI 6390-2011 on Energy Conservation for Air Conditioners in Buildings

Source: International Energy Agency
Last updated: 20 May 2021

This standard provides guidance on air conditioners for any person involved in planning, implementation, monitoring and building management. The standard comprises technical planning, operation and maintenance, energy conservation, testing and energy analysis.



 



Minimum efficiency of electrically operated air conditioning equipment:



split < 65.000 BTU/h: COP 2.70; KW/TR 1.303



Variable Refrigerant Value: COP 3,70; KW/TR 0.951



Split Duct: COP 2.60; KW/TR 1,353



Air Cooled Chiller < 150 TR (recip): COP 2.80; KW/TR 1.256



Air Cooled Chiller < 150 TR (screw): COP 2.90; KW/TR 1.213



Air Cooled Chiller> 150 TR (recip): COP 2.80; KW/TR 1.256



Air Cooled Chiller > 150 TR (screw): COP 3.00; 1.172



Water Cooled Chiller < 150 TR (recip): COP 4.00; KW/TR 0.879



Water Cooled Chiller < 150 TR (screw): COP 4.70; KW/TR 0.859



Water Cooled Chiller > 150 TR (recip): COP 4.26; KW/TR 0.826



Water Cooled Chiller > 150 TR (screw): COP 4.40; KW/TR 0,799



Water Cooled Chiller > 300 TR (centrifugal). COP 6.05; KW/TR 0.581



 



This standard was developed starting from SNI 03-6197.