ISIRI 10636 Fan coils and ducted fan coils - technical specifications and test method for energy consumption and energy labeling instruction

Source: International Energy Agency
Last updated: 04 August 2020

Energy efficiency classes for CFM 200 fan coils (ground, ceiling):




  • Class A


    • Cooling Capacity: <8.0 W/(1000Btu/h)

    • Heating Capacity: <3.8 W/(1000Btu/h)


  • Class B


    • Cooling Capacity: 8.0=Y<9.5

    • Heating Capacity: 3.8=X<4.0


  • Class C


    • Cooling Capacity: 9.5=Y<11.0

    •  Heating Capacity: 4.0=X<4.4


  • Class D


    • Cooling Capacity: 11=Y<12.4

    • Heating Capacity: 4.4=X<4.8


  • Class E


    • Cooling Capacity: 12.4=Y<14.0

    • Heating Capacity: 4.8=X<5.7


  • Class F


    • Cooling Capacity: 14.0=Y<15.5

    • Heating Capacity: 5.7=X<5.9


  • Class G


    • Cooling Capacity: 15.5=Y<17.0

    • Heating Capacity: 5.9=X<6.2




 



Energy efficiency classes for CFM 300 (ground, ceiling) fan coils:




  • Class A


    • Cooling Capacity: Y<7.0

    • Heating Capacity: X<2.4


  • Class B


    • Cooling Capacity: 7.0=Y<7.5

    • Heating Capacity: 2.4=X<2.7


  • Class C


    • Cooling Capacity: 7.5=Y<8.5

    •  Heating Capacity:  2.7=X<3.1


  • Class D


    • Cooling Capacity:  8.5=Y<9.5

    • Heating Capacity: 3.1=X<3.5


  • Class E


    • Cooling Capacity: 9.5=Y<10.5

    • Heating Capacity: 3.5=X<3.9


  • Class F


    • Cooling Capacity: 10.5=Y<11.5

    • Heating Capacity:  3.9=X<4.3


  • Class G


    • Cooling Capacity: 11.5=Y<12.5  

    • Heating Capacity: 4.3=X<4.7


Want to know more about this policy ? Learn more (Persian)