Energy efficiency requirement for chillers

Source: International Energy Agency
Last updated: 22 July 2020

This standard defines EER and COP of air cooled and water cooled chillers, starting from 2003 (first phase) and 2005 (second phase)



 



water cooled,volume compressor  




  • CC <150RT


    • first phase: EER 3.50; COP4.07

    • second phase: EER 3.83; COP4.45  


  • CC ?150RT and ?500RT


    • first phase: EER 3.60; COP 4.19

    • second phase: EER 4.21; COP 4.90


  • CC> 500


    • first phase: EER (kcal/h-W)4.00; COP 4.65

    • second phase: EER (kcal/h-W)4.73; COP 5.50




water cooled,centrifugal compressor  




  • CC <150RT


    • first phase:EER (kcal/h-W)4.30; COP 5.00

    • second phase: CC EER (kcal/h-W)4.3 COP 5.00


  • CC ?150RT and <300RT


    • first phase: EER (kcal/h-W)4.77; COP 5.55

    • Second phase: EER (kcal/h-W)4.77; COP 5.55


  • CC ?300RT


    • first phase: EER (kcal/h-W)4.77; COP 5.55

    • second phase: EER (kcal/h-W)5.25; COP 6.10




 



air cooled:




  • first phase: EER 2.40; COP 2.79

  • second phase: EER 2.40; COP 2.79



 

Want to know more about this policy ? Learn more (Chinese)