GB 19577-2015: Minimum Energy Performance Standards for water chillers

Source: International Energy Agency
Last updated: 16 April 2021

MEPS for electric water chiller with vapor compression cycle. Energy performance, here indicated through Integrated Part Load Value (IPLV) for different capacity ranges are:


 


air-cooled or evaporating cooled



  • CC = 50 kW: COP 2.50, IPLV 2.80;  

  • CC  > 50 kW: COP 2.70, IPLV 2.90; water-cooled:  


 


water-cooled



  • CC = 528 kW: COP 4.20, IPLV 5.00;  

  •  528 kW < CC = 1163 kW: COP4.70, IPLV 5.50;

  •  CC > 1163 kW: COP 5.20, IPLV 5.90


 


IPLV = Integrated Part Load Value


CC = Cooling capacity


COP= Coefficient of Performance

Want to know more about this policy ? Learn more (Chinese)