Electric Chillers with over 350kW of capacity

Last updated: 3 June 2020

As of December 2012 Chillers with capacities greater than 350kW sold in Australia must comply with the minimum energy

performance standards (MEPS) regulations.

 

Capacity: 350-499

  • Minimum COP
    • Air cooled 2.70
    • Water cooled 5.00
  • Minimum IPLV
    • Air cooled 3.70
    • Water cooled 5.50

Capacity: 500-699

  • Minimum COP
    • Air cooled 2.70
    • Water cooled 5.10
  • Minimum IPLV
    • Air cooled 3.70
    • Water cooled 6.00

Capacity: 700-999

  • Minimum COP
    • Air cooled 2.70
    • Water cooled 5.50
  • Minimum IPLV
    • Air cooled 4.10
    • Water cooled 6.20

Capacity: 1,000-1,499

  • Minimum COP
    • Air cooled 2.70
    • Water cooled 5.80
  • Minimum IPLV
    • Air cooled 4.10
    • Water cooled 6.50

Capacity: >1,500

  • Minimum COP
    • Air cooled 2.70
    • Water cooled 6.00
  • Minimum IPLV
    • Air cooled 4.10
    • Water cooled 6.50

Want to know more about this policy ? Learn more