MEPS for Air Conditioners
Morocco adopted Air Conditioners Minimum Energy Performance Standards (MEPS) in June 2018
Air cooled Air conditioners:
- Split and Multi-split Air Conditioners
- cooling EER > 2.8
- heating COP > 3.2
- Monobloc Air Conditioners
- cooling EER > 3.1
- heating COP > 3.2
Water cooled air conditioners:
- Split and Multi-split Air Conditioners
- cooling EER> 2.6
- heating COP> 3.0
- Monobloc Air Conditioners
- cooling EER> 3.8
- heating COP> 3.0
EER= Energy efficiency ration
COP= coefficient of performance