MEPS: Air Conditioners 2018

Last updated: 10 May 2019

Minimum Energy Performance Standards:

Unit of Measure COPW = 0.4 COP100% + 0.6 COP50%

WINDOW :

2.90 COP100% for <30000 BTU/hr [8.8 kW]

SINGLE SPLIT NON-INV:

3.78 COP100% for < 600000 BTU/hr [17.6 kW]

MULTI SPLIT NON-INV:

3.78 COP100% for < 600000 BTU/hr [17.6 kW]

SINGLE SPLIT INV:

3.78 COP100% for < 600000 BTU/hr [17.6 kW]

3.34 COPW for < 600000 BTU/hr [17.6 kW]

MULTI SPLIT INV:

3.78 COP100% for < 600000 BTU/hr [17.6 kW]

3.34 COPW for < 600000 BTU/hr [17.6 kW]

TEST STANDARDS

Casement, window and single-split:

ISO 5151:2010

Section 5.1: Cooling capacity test

Climate Class T1

Multi-split:

ISO 15042:2011

Section 6.1: Cooling capacity test

Climate Class T1

All

(for standby power) IEC 62301:2005 or

IEC 62301:2011  Section 5.3.1 or 5.3.2 of

IEC 62301:2005 or Section 5.3.2, 5.3.3 or 5.3.4 of IEC 62301:2011

Want to know more about this policy ? Learn moreLearn more

End uses covered
  • Building end-uses
  • Building systems
  • Space cooling