MEPS for electric water chiller with vapor compression cycle. Energy performance, here indicated through Integrated Part Load Value (IPLV) for different capacity ranges are:

 

air-cooled or evaporating cooled

  • CC = 50 kW: COP 2.50, IPLV 2.80;  
  • CC  > 50 kW: COP 2.70, IPLV 2.90; water-cooled:  

 

water-cooled

  • CC = 528 kW: COP 4.20, IPLV 5.00;  
  •  528 kW < CC = 1163 kW: COP4.70, IPLV 5.50;
  •  CC > 1163 kW: COP 5.20, IPLV 5.90

 

IPLV = Integrated Part Load Value

CC = Cooling capacity

COP= Coefficient of Performance